TD358Y Vakuum Unterbrecher
Basisinformation
Modell: VITD 12/2500-40Y
Produktbeschreibung
Vakuum Unterbrecher
VITD 12/2500-40Y
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS | |
1.Rated Frequency | 50/60Hz |
2.Rated Maximum Line to Line Voltage | 12kV,r.m.s |
3.Rated Power Frequency Withstand Voltage:Air | 42kV,r.m.s |
4.Rated Impulse Withstand Voltage:Air | 95kV,Peak |
5.Rated Normal Current | 2500A |
6.Rated Short-Circuit Current(3Phase Symmetrical Basis) | 40kA,r.m.s |
7.Percentage D.C. Component of Rated S.C. Breaking Current | 50% |
8.Rated Short-Circuit Making Current | 100kA,Peak |
9.Rated Duration of Short Time Current | 4s |
10.Rated Short-Time Withstand Current | 40kA,r.m.s |
11.Rated Peak Withstand Current | 100kA,r.m.s |
12.*Maximum Contact Resistance at Minimum Closing Force | 16Micro ohms |
13.*Rated Breaking Current of Single Capacitor Bank | 630A,r.m.s |
14.*Rated Breaking Current of Back-to-Back Capacitor Bank | 400A,r.m.s |
15.Rated operating sequence | o-0.3s-co-180s-co |
MECHANICAL DATA | |
1.Interrupter Weight(Approx.) | 6.19kg |
2.Moving Part Weight(Approx.) | 2.24kg |
3.Closing Force due to Bellow and Atmospheric | 21050N |
4.Force Required to Hold Contacts open at Full Stroke | 35060N |
MECHANICAL REQUIREMENTS(REF. VCB) | |
1.Contact Stroke | 111 mm |
2.Opening Speed(average of 75 contact gap) | 1.10.2m/Sec |
3.Maximum Overtravel During Opening | 2mm |
4.Maximun Rebound During Opening | 2mm |
5.Closing Speed(average of last 30% contact gap) | 0.60.2m/Sec |
6.Maximum Contact Bounse Duration(with maximum 2 bounces) | 2ms |
7.Rated Contact Compressive Force | 3150200N |
8.Closing and Opening non-simultaneity of three-phase Contacts | 2ms |
LIFE (ESTIMATED) | |
1.Electrical Life at Rated Normal Current | 50,000Operations |
2.Electrical Life at Rated Short Circuit Current | 50Operations |
3.Mechanical Life | 50,000Operations |
4.Contact Erosion Limit | 3mm |
5.Shelf Life | 20Years |
1.Meets or exceeds the electrical endurance requirements of class E2 for autoreclosing duty per IEC 62271-200 and JB 8738-2008. 2.* Rated Characteristics to be given on request |
Produktgruppe : Vakuum-Schaltkammer
Premium Related Products
andere Produkte
heiße Produkte
TD324P Vakuum UnterbrecherTD324Y Vakuum UnterbrecherTD325J Vakuum UnterbrecherTD325K Vakuum UnterbrecherTD325Y Vakuum UnterbrecherTD326E Vakuum UnterbrecherTD326Y Vakuum UnterbrecherTD336G Vakuum UnterbrecherTD336Y Vakuum UnterbrecherTD358Y Vakuum UnterbrecherTD368Y Vakuum UnterbrecherTD424B Vakuum UnterbrecherTD425Y Vakuum UnterbrecherTD445Z Vakuum UnterbrecherTD524A Vakuum UnterbrecherTD544H Vakuum Unterbrecher