Finden Sie Vakuum-Schaltkammer auf Industry Directory, zuverlässige Hersteller / Lieferant / Fabrik aus China

Anfrage-Korb (0)
Home > Produkt-Liste > Vakuum-Schaltkammer > TJ040K Vakuum Unterbrecher

TJ040K Vakuum Unterbrecher

Basisinformation

Modell: VITJ 1.14/1600K

Produktbeschreibung

Vakuum Unterbrecher für Schütz

VITJ 1.14 / 1600K

ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS 
1.Rated Frequency 50/60Hz 
2.Rated Maximum Line to Line Voltage 1.14kV,r.m.s 
3.Rated Power Frequency Withstand Voltage:Air 10kV,r.m.s 
4.Rated Impulse Withstand Voltage:Air 15kV,Peak 
5.Rated Normal Current 1600/2000A 
6.Maximum Contact Resistance at Minimum Closing Force 50Micro ohms 
7.Rated Making Current 6.3/10kA
8.Rated Breaking Current 5.0/8.0kA
9.Rated Breaking Current(Max) 6.3/10kA
10.Rated Breaking Current(Min) 320/400A
11.Rated Short-Time Withstand Current 5.0/8.0kA
12.Rated Duration of Short Time Current 4s
MECHANICAL DATA
1.Interrupter Weight(Approx.) 1.34kg 
2.Moving Part Weight(Approx.) 0.47kg 
3.Closing Force due to Bellow and Atmospheric 7020N
4.Force Required to Hold Contacts open at Full Stroke 11030N
MECHANICAL REQUIREMENTS(REF. VC) 
1.Contact Stroke 4.51 mm 
2.Opening Speed(average of 75 contact gap) 0.60.2m/Sec 
3.Closing Speed(average of last 30% contact gap) 0.30.1m/Sec 
4.Contact Bounce Duration at Closing Operation 3ms
5.Closing and Opening non-simultaneity of three-phase Contacts 1ms
6.Maximum Rebound during opening 2mm
7.Rated Contact Compressive Force 20010N 
LIFE (ESTIMATED) 
1.Electrical Endurance AC-3 250,000Operations 
2.Electrical Endurance AC-4 100,000Operations
3.Mechanical Life 500,000Operations 
4.Contact Erosion Limit 3mm 
5.Shelf Life 20Years

Produktgruppe : Vakuum-Schaltkammer